Multi Core, PVC Insulated, PVC Sheathed Cables
(H05VV – R , H05VV – U , NYM)
No. & Nominal Cross Section of Conductors (mm²) | Class of Conductor | Nomina Insulati Thickne (mm) | Approx.Filler Thickness (mm) | Nominal Sheath Thickness (mm) | Average Outer Diameter min. (mm) | Average Outer Diameter max. (mm) | Max. Conductor Resistance at 20 °c ( Ω / Km ) | Approx. Weight (Kg / Km) |
---|---|---|---|---|---|---|---|---|
2×1.5 | 1 | 0.7 | 0.4 | 1.2 | 7.6 | 10 | 12.1 | 114 |
2×1.5 | 2 | 0.7 | 0.4 | 1.2 | 7.8 | 10.5 | 12.1 | 123 |
2×2.5 | 1 | 0.8 | 0.4 | 1.2 | 8.6 | 11.5 | 7.41 | 156 |
2×2.5 | 2 | 0.8 | 0.4 | 1.2 | 9 | 12 | 7.41 | 168 |
2×4 | 1 | 0.8 | 0.4 | 1.2 | 9.6 | 12.5 | 4.61 | 201 |
2×4 | 2 | 0.8 | 0.4 | 1.2 | 10 | 13 | 4.61 | 219 |
2×6 | 1 | 0.8 | 0.4 | 1.2 | 10.5 | 13.5 | 3.08 | 261 |
2×6 | 2 | 0.8 | 0.4 | 1.2 | 11 | 14 | 3.08 | 282 |
2×10 | 1 | 1 | 0.6 | 1.4 | 13 | 16.5 | 1.83 | 428 |
2×10 | 2 | 1 | 0.6 | 1.4 | 13.5 | 17.5 | 1.83 | 459 |
2×16 | 2 | 1 | 0.6 | 1.4 | 15.5 | 20 | 1.15 | 632 |
2×25 | 2 | 1.2 | 0.8 | 1.4 | 18.5 | 24 | 0.727 | 957 |
2×35 | 2 | 1.2 | 1 | 1.6 | 21 | 27.5 | 0.524 | 1276 |
2×1.5 | 1 | 0.7 | 0.4 | 1.2 | 8 | 10.5 | 12.1 | 133 |
3×1.5 | 2 | 0.7 | 0.4 | 1.2 | 8.2 | 11 | 12.1 | 143 |
3×2.5 | 1 | 0.8 | 0.4 | 1.2 | 9.2 | 12 | 7.41 | 186 |
3×2.5 | 2 | 0.8 | 0.4 | 1.2 | 9.4 | 12.5 | 7.41 | 199 |
3×4 | 1 | 0.8 | 0.4 | 1.2 | 10 | 13 | 4.61 | 245 |
3×4 | 2 | 0.8 | 0.4 | 1.2 | 10.5 | 13.5 | 4.61 | 265 |
3×6 | 1 | 0.8 | 0.4 | 1.4 | 11.5 | 14.5 | 3.08 | 336 |
3×6 | 2 | 0.8 | 0.4 | 1.4 | 12 | 15.5 | 3.08 | 359 |
3×10 | 1 | 1 | 0.6 | 1.4 | 14 | 17.5 | 1.83 | 532 |
3×10 | 2 | 1 | 0.6 | 1.4 | 14.5 | 19 | 1.83 | 564 |
3×16 | 2 | 1 | 0.8 | 1.4 | 16.5 | 21.5 | 1.15 | 811 |
3×25 | 2 | 1.2 | 0.8 | 1.6 | 20.5 | 26 | 0.727 | 1227 |
3×35 | 2 | 1.2 | 1 | 1.6 | 22 | 29 | 0.524 | 1614 |
4×1.5 | 1 | 0.7 | 0.4 | 1.2 | 8.6 | 11.5 | 12.1 | 159 |
4×1.5 | 2 | 0.7 | 0.4 | 1.2 | 9 | 12 | 12.1 | 170 |
4×2.5 | 1 | 0.8 | 0.4 | 1.2 | 10 | 13 | 7.41 | 224 |
4×2.5 | 2 | 0.8 | 0.4 | 1.2 | 10 | 13.5 | 7.41 | 240 |
4×4 | 1 | 0.8 | 0.4 | 1.4 | 11.5 | 14.5 | 4.61 | 310 |
4×4 | 2 | 0.8 | 0.4 | 1.4 | 12 | 15 | 4.61 | 335 |
4×6 | 1 | 0.8 | 0.6 | 1.4 | 12.5 | 16 | 3.08 | 423 |
4×6 | 2 | 0.8 | 0.6 | 1.4 | 13 | 17 | 3.08 | 454 |
4×10 | 1 | 1 | 0.6 | 1.4 | 15.5 | 19 | 1.83 | 656 |
4×10 | 2 | 1 | 0.6 | 1.4 | 16 | 20.5 | 1.83 | 693 |
4×16 | 2 | 1 | 0.8 | 1.4 | 18 | 23.5 | 1.15 | 1002 |
4×25 | 2 | 1.2 | 1 | 1.6 | 22.5 | 28.5 | 0.727 | 1550 |
4×35 | 2 | 1.2 | 1 | 1.6 | 24.5 | 32 | 0.524 | 2011 |
5×1.5 | 1 | 0.7 | 0.4 | 1.2 | 9.4 | 12 | 12.1 | 185 |
5×15 | 2 | 0.7 | 0.4 | 1.2 | 9.8 | 12.5 | 12.1 | 199 |
5×2.5 | 1 | 0.8 | 0.4 | 1.2 | 11 | 14 | 7.41 | 264 |
5×25 | 2 | 0.8 | 0.4 | 1.2 | 11 | 14.5 | 7.41 | 282 |
5×4 | 1 | 0.8 | 0.6 | 1.4 | 12.5 | 16 | 4.61 | 382 |
5×4 | 2 | 0.8 | 0.6 | 1.4 | 13 | 17 | 4.61 | 411 |
5×6 | 1 | 0.8 | 0.6 | 1.4 | 13.5 | 17.5 | 3.08 | 506 |
5×6 | 2 | 0.8 | 0.6 | 1.4 | 14.5 | 18.5 | 3.08 | 539 |
5×10 | 1 | 1 | 0.6 | 1.4 | 17 | 21 | 1.83 | 784 |
5×10 | 2 | 1 | 0.6 | 1.4 | 17.5 | 22 | 1.83 | 827 |
5×16 | 2 | 1 | 0.8 | 1.6 | 20.5 | 26 | 1.15 | 1222 |
5×25 | 2 | 1.2 | 1 | 1.6 | 24.5 | 31.5 | 0.727 | 1859 |
5×35 | 2 | 1.2 | 1.2 | 1.6 | 27 | 35 | 0.524 | 2454 |
Technical Data
- PVC insulated, PVC sheathed cables for wiring and industrial purposes.
Nominal voltage Uo/ U
- 300/500V
Reference Standard
- IEC 60227-4
Cable code
- 60227 IEC 10
- H05VV-R
- H05VV-U
- NYM
Temperature range
- -30℃ to +70℃
Cable Layer Construction
- Cu/PVC/PVC
Cable Structure
- Conductor material : copper conductor according to IEC 60228, class 1( solid ) for conductors up to and including 16 mm², class 2 (stranded) for all sizes of conductors.
- PVC core insulation : Compound type of PVC/ C.
- Core insulation colors : According to IEC 60227 - 1.
- PVC inner covering.
- PVC outer sheath: Compound type of PVC/ ST4.
- Sheath color is normally black..
- These Types of cables can also be manufactured with aluminium or aluminium alloy conductors, according to IEC 60228.
Application
These types of cables are used in, on and under plaster in dry, wet and damp rooms as well as brick work
or concrete, with the exception of direct laying of reinforce, vibrated or compressed concrete. Outdoor
usage, only with protection against direct sunlight, is permitted.