Low Smoke/Haloge Free Flexible Conductors

 (Cu/LSZH)

Attributes
Nominal Cross Section of Conductors ( mm2 )Class of
Conduct
or
Nominal Insulation Thickness
(mm )
Nominal Outer
Diameter
( mm )min
Nominal Outer
Diameter
( mm )max
Max Conductor
Resistance at 20℃
( Ω⁄Km )
Approx Weight
(Kg / Km)
1×150.62.42.919.517
1×1.550.72.83.513.325
1×2.550.83.44.37.9835
1×450.83.94.94.9552
1×650.84.45.53.374
1×10515.77.11.91124
1×16516.78.41.21183
1×2551.28.410.60.78276
1×3551.29.712.10.554372
1×5051.411.514.40.386524
1×7051.413.216.60.272718
1×9551.615.118.80.206973
1×12051.616.720.90.1611220
1×15051.818.623.30.1291543
1×1855220.625.80.1061860
1×24052.223.529.40.08012400
Description

Technical Data

  • Single Core, LSZH insulated, Flexible Conductors.

Cable Code

  • H05Z – K
  • H07Z – K

Nominal Voltage:

  • 300 / 500 V, for conductors up to 1mm² cross section
  • 450 / 750 V, for conductors with a cross section of more than 1mm²

Reference Standard

  • BS 7211
  • IEC 60332-1
  • BS EN 50525-3-31
  • IEC 60754-1,2
  • IEC 61034-1,2

Temperature range

  • −40 ℃ to +90 ℃

 Cable Layers Construction

  • Cu/ LSZH

Cable Structure

  • Conductor material: Flexible annealed copper conductor according to the IEC 60228 (ISIRI 3084), class 5 (flexible)
  • Insulation material: Low Smoke/Halogen free (LSZH) compound.
  • Insulation Identification: As per customer request.

Application

Due to their better durability and resistivity in case of fire, where these type of wires would
not emit hazardous and halogenated gases, they are used for distribution of electrical energy
for fixed installations in underground, indoors, industrial and public facilities, train stations
and subways.