Multi Core, XLPE Insulated, Wire/ Tape Armored, PVC Sheathed Cable (N2XRY , N2XBY )

Attributes
No. & nominal Cross Section of the conductors
(mm²)
NominaI Insulation Thickness
(mm)
Filler Thickness(mm)steel Wire Diameter(mm)Nominal Sheath Thickness
(mm)
Average Outer Diameter (mm)Maximum conductor Resistance at 20℃
(Ω / Km)
Approx. weight
(Kg / Km)
2×1.50.710.81.812.812.1306
2×2.50.710.81.813.67.41355
2×40.710.81.814.54.61418
2×60.710.81.815.53.08494
2×100.711.251.8181.83766
2×160.711.251.821.11.151043
2×250.911.61.825.20.7271558
2×350.911.61.827.90.5241930
3×1.50.710.81.813.212.1333
3×2.50.710.81.814.17.41393
3×40.710.81.8154.61468
3×60.710.81.816.23.08570
3×100.711.251.818.81.83875
3×160.711.251.822.11.151213
3×250.911.61.826.50.7271842
3×350.911.61.829.40.5242301
4×1.50.710.81.813.912.1372
4×2.50.710.81.814.97.41443
4×40.710.81.8164.61537
4×60.711.251.818.13.08786
4×100.711.251.820.11.831022
4×160.711.61.824.51.151575
4×250.911.61.828.60.7272184
4×350.911.61.832.10.5242776
5×1.50.710.81.814.712.1410
5×2.50.710.81.815.87.41499
5×40.711.251.817.94.61729
5×60.711.251.819.33.08895
5×100.711.251.821.51.831182
5×160.711.61.826.41.151829
5×250.911.61.8310.7272540
5×350.911.61.8350.5243262
6×1.5110.81.815.512.1468
7×1.5110.81.815.512.1470
10×1.510.41.251.819.212.1759
12×1.51.0.41.251.819.612.1805
14×1.510.41.251.820.312.1873
16×1.510.41.251.821.112.1942
19×1510.41.61.823.612.11229
21×1.510.41.61.823.612.11257
24×1.510.41.61.825.412.11431
30×1.510.41.61.826.612.11599
37×1.510.41.61.929.312.11948
6×2.510.41.251.817.67.41683
7×2.511.251.251.817.67.41690
10×2.511.251.251.820.77.41924
12 × 2.511.2511.821.27.41987
14 × 2.511.2511.8227.411074
16 × 2.511.611.823.67.411293
19 × 2.511.611.825.67.411520
21 × 2.511.611.825.67.411564
24×2.511.611.827.77.411776
30×2.511.611.929.27.412019
37×2.511.61232.37.412483
Description

Technical Data

  • Power and control cables, XLPE insulated, wire or tape armored, PVC sheathed for energy supply and control applications.

Nominal voltage Uo / U

  • 0.6/1kV

Main standard

  • IEC 60502 - 1

Cable code

  • N2XRY
  • N2XBY

Temperature range

  • - 40 to+ 90 °C

Cable Layer Construction

  • Cu /XLPE / Bd / SWA/ PVC
  • Cu/ XLPE / Bd / DTA/ PVC

Cable Structure

  • Conductor material: Bare copper conductor according to IEC 60228, class 1 ( solid ), class 2 ( stranded ) or class 5 ( flexible )
  • XLPE core insulation: Cross linked polyethylene compound
  • Core insulation colors: As per customer request
  • PVC inner covering.
  • Armour: Galvanized steel wire or tape.
  • PVC outer sheath: Compound type of PVC/ ST2.
  • Sheath color is normally black.
  • These Types of cables can also be manufactured with aluminium or aluminium alloy conductors, according to IEC 60228

Application

These types of cables are used for distribution of electrical energy supply and control applications for fixed installations in underground, cable ducts, indoors, in water and open air where more mechanical protection isrequired.

In addition, XLPE insulation material has better mechanical, electrical, chemical and durability characteristics than PVC