Single Core, PVC Insulated, Rigid Conductors
(H05V – U , H07V – U , H07V – R , NYA)
Nominal Cross Section of Conductors (mm²) | Class of conductor | Nominal Insulation Tickness (mm) | Average Outer Diameter (mm) Min | Average Outer Diameter (mm) Max | Max. Conductor Resistance at 20 °c ( Ω / Km ) | Approx. Weight ( Kg / Km ) |
---|---|---|---|---|---|---|
0.5 | 1 | 0.6 | 1.9 | 2.3 | 36 | 8 |
0.75 | 1 | 0.6 | 2.1 | 2.5 | 24.5 | 11 |
1 | 1 | 0.6 | 2.2 | 2.7 | 18.1 | 13 |
1.5 | 1 | 0.7 | 2.6 | 3.2 | 12.1 | 19 |
1.5 | 2 | 0.7 | 2.7 | 3.3 | 12.1 | 21 |
2.5 | 1 | 0.8 | 3.2 | 3.9 | 7.41 | 30 |
2.5 | 2 | 0.8 | 3.3 | 4 | 7.41 | 33 |
4 | 1 | 0.8 | 3.6 | 4.4 | 4.61 | 44 |
4 | 2 | 0.8 | 3.8 | 4.6 | 4.61 | 48 |
6 | 1 | 0.8 | 4.1 | 5 | 3.08 | 62 |
6 | 2 | 0.8 | 4.3 | 5.2 | 3.08 | 67 |
10 | 1 | 1 | 5.3 | 6.4 | 1.83 | 104 |
10 | 2 | 1 | 5.6 | 6.7 | 1.83 | 111 |
16 | 2 | 1 | 6.4 | 7.6 | 1.15 | 169 |
25 | 2 | 1.2 | 8.1 | 9.7 | 0.727 | 264 |
35 | 2 | 1.2 | 9 | 10.9 | 0.524 | 354 |
50 | 2 | 1.4 | 10.6 | 12.8 | 0.387 | 484 |
70 | 2 | 1.4 | 12.1 | 14.6 | 0.268 | 677 |
95 | 2 | 1.6 | 14.1 | 17.1 | 0.193 | 933 |
120 | 2 | 1.6 | 15.6 | 18.8 | 0.153 | 1163 |
150 | 2 | 1.8 | 17.3 | 20.9 | 0.124 | 1436 |
185 | 2 | 2 | 19.3 | 23.3 | 0.0991 | 1793 |
240 | 2 | 2.2 | 22 | 26.6 | 0.0754 | 2343 |
300 | 2 | 2.4 | 24.5 | 29.6 | 0.0601 | 2934 |
400 | 2 | 2.6 | 27.5 | 33.2 | 0.047 | 3726 |
Technical Data
- PVC single core, non sheathed with rigid conductor for general purposes.
Nominal Voltage Uo / U
- 300 / 500 V for conductors up to and including 1mm²
- 450 / 750 V for conductors above 1mm²
Reference Standard
- IEC 60227-3
Cable code
- 60227 IEC 05 ( H05V - U )
- 60227 IEC 01 ( HO7V - U )
- 60227 IEC 01 ( HO7V- R )
- NYA
Temperature range
- - 30℃ to + 70℃
Cable Layer Construction
- Cu / PVC
Cable Structure
- Conductor material: Annealed copper conductor according to IEC 60228, class 1 ( solid ) or class 2 ( stranded ).
- PVC core insulation: Compound type of PVC/ C
- Core insulation colors: As per customer request.
Application
These types of cables are used for fixed installations as connecting cables in underground cable ducts, machines and distribution boards. They can be used in control cabinet structures and with stranded conductors as hook up wires.
Laying in tubes and under plaster is permitted.