Off-Shore Multi-core Power Cables, XLPE insulated, LSZH sheathed

کابل های قدرت (ساده / شیلددار)
Property
Nominal Cross Section of Conductors ( mm² )Class of ConductorsMica Tape Thickness
(mm)
Nominal Insulation
Thickness( mm )
Nominal. Inner Covering Thickness ( mm ) Nominal Diameter of braid armor
( mm )
Nominal Sheath
Thickness
( mm )
Nominal Outer Diameter
( mm )
Max. Conductor Resistance at 20℃
(Ω/Km )
Approx. Weight
(Kg/Km)
Cable structure:
Cu (TiCu) / XLPE / LSZH
3×2.52-0.7--1.19.67.41143
Cable structure:
Cu (TiCu) / XLPE / Bd / CWB (TiCWB) / LSZH
3×2.52-0.71.10.21.212.77.41274
Cable structure:
Cu (TiCu) / XLPE / Bd / SWB / LSZH
3×2.52-0.71.10.21.212.77.41268
Cable structure:
Cu (TiCu) / MGT / XLPE / LSZH
3×2.520.120.7--1.111.77.41158
Cable structure:
Cu (TiCu) / MGT / XLPE / Bd / CWB (TiCWB) / LSZH
3×2.520.120.71.10.21.2157.41310
Cable structure:
Cu (TiCu) / MGT / XLPE / Bd / SWB / LSZH
3×2.520.120.71.10.21.2157.41303
Description

Technical Data 

  • Off-shore Multi-core Power cables, XLPE insulated, LSZH sheathed


Rated voltage

  • 0.6/1kV


Reference standard

  • IEC 60092-353
  • IEC 60092-360
  • IEC 60332-1,3
  • IEC 60754-1,2
  • IEC 61034-1,2
  • IEC 60331-21


Temperature range

  • −40 ℃ to +90 ℃

Cable Layers Construction

  • Cu(TiCu)/XLPE/LSZH
  • Cu(TiCu)/XLPE/Bd/CWB(TiCWB)/LSZH
  • Cu(TiCu)/XLPE/Bd/SWB/LSZH
  • Cu(TiCu)/MGT/XLPE/LSZH
  • Cu(TiCu)/MGT/XLPE/Bd/CWB(TiCWB)/LSZH
  • Cu(TiCu)/MGT/XLPE/Bd/SWB/LSZH

Cable Structure

  • Conductor material: Plain or tinned annealed copper according to the IEC 60228 (ISIRI 3084), class 2 (stranded) or class 5 (flexible)
  • Tape: Mica tape (if any)
  • Insulation material: XLPE compound
  • Core Identification: As per customer request
  • Bedding Material: An extruded bedding compound same as the outer sheath material.
  • Braid Armor: Plain or tinned annealed copper or galvanized steel (if any)
  • Outer Sheath material: Low Smoke/Halogen Free (LSZH) compound
  • Outer Sheath color: As per customer request

Application

These types of cables are used on off-shore drilling platforms, ships/vessels and off-shore structures as for electronics and electro mechanic systems, lighting and power supply systems.