Single Core, XLPE Insulated, PVC/ PE Sheathed, Power Cables
N2XY , N2X2Y

Property
The nominal cross-section of the conductors
(mm²)
Conductor classNominal insulation thickness(mm)Nominal sheath thickness
(mm)
Average final diameter
(mm)
Max. Conductor
Resistance at 20 °c
( Ω / Km )
Approximate weight(Kg / Km)
610.71.46.93.0892
620.71.47.33.0897
1010.71.47.71.83136
1020.71.48.21.83147
1620.71.49.21.15209
2520.91.410.90.727312
3520.91.4120.524412
50211.413.60.387540
7021.11.415.50.268749
9521.11.517.60.1931027
12021.21.519.30.1531265
15021.41.621.50.1241571
18521.61.623.80.09911952
24021.71.726.70.07542539
30021.81.829.50.06013048
400221.933.20.0474024
50022.2237.20.03665132
Description

Technical Data

  • Power cables, XLPE insulated, PVC or PE sheathed for energy supply

Nominal voltage Uo / U

  • 0.6/ 1kV

Main standard

  • IEC 60502 – 1

Cable code

  • N2XY
  • N2X2Y

Temperature range

  • - 30℃ to + 90℃

Cable Layer Construction

  • Cu / XLPE / PVC
  • Cu / XLPE / PE

Cable Structure

  • Conductor material: Annealed copper conductor according to IEC 60228, class 1 ( solid ), class 2 ( stranded ) or class 5 ( flexible ).
  • XLPE core insulation: Cross linked polyethylene compound
  • Core insulation color: As per customer request
  • Outer sheath: Compound type of PVC/ ST2, or Low Density Polyethylene ( LDPE )
  • Sheath color is normally black
  • These Types of cables can also be manufactured with aluminium or aluminium alloy conductors, according to IEC 60228

Application

These types of cables are used for distribution of electrical energy for fixed installations in underground, cable ducts, power stations, indoors, in water and open air where mechanical damages are not expected.

In addition, XLPE insulation material has better mechanical, electrical, chemical and durability characteristics than PVC.